Skip to content
Module 10 of 10 180m 4 exam Qs

System Testing & Commissioning

DWV testing methods, water supply pressure testing, final inspection, and commissioning procedures.

  • Describe water test and air test procedures for DWV systems
  • Explain water supply pressure testing requirements
  • Outline the final inspection and commissioning process

Lesson 1

DWV Water Test & Air Test Procedures

DWV Water Test

The water test is the most common and reliable method for testing DWV systems. It verifies that all joints are leak-free before the system is concealed behind walls and ceilings.

1
Plug All Openings
Cap or plug all drain, vent, and cleanout openings
2
Fill With Water
Fill to the highest opening (roof vent)
3
Hold Pressure
Maintain water level for required duration
4
Inspect
Check every joint for leaks

Water Test Requirements

  • Fill the system to the highest opening (usually the roof vent)
  • Maintain water level for the duration specified by code (typically 15 minutes minimum)
  • Visually inspect every joint, fitting, and connection for leaks
  • Any drop in water level indicates a leak that must be found and repaired
  • Retest after repairs

DWV Air Test

The air test is an alternative when a water test is not practical (cold weather, inaccessible locations). Air testing uses compressed air at a specified pressure:

35 kPa
Typical Air Test Pressure (5 psi)
15 min
Minimum Hold Time
⚠️

Air Test Caution

Air under pressure stores energy. If a fitting fails during an air test, it can become a projectile. Never exceed the specified test pressure and ensure all plugs and caps are properly secured.

Key Takeaway

The water test fills the DWV system to the highest opening and checks for leaks visually. The air test uses approximately 35 kPa (5 psi) and holds for at least 15 minutes. Both tests must show zero leaks before the system can be concealed.