Skip to content
Módulo 3 de 8 90m 15 exam Qs

Electrical Troubleshooting - Capacitors, Contactors & Motor Testing

Capacitor testing and diagnosis, contactor evaluation, single-phase and three-phase motor testing, and compressor electrical analysis using multimeters and megohmmeters.

  • Test capacitors for proper MFD value, leakage, and intermittent failure
  • Evaluate contactor condition through voltage drop testing and visual inspection
  • Perform comprehensive motor testing including winding resistance and megohm testing
  • Diagnose single-phase compressor electrical failures using the CSR method

Lección 1

Capacitor Testing & Diagnosis

How Capacitors Fail

Capacitors are the most frequently replaced component in residential HVAC systems. They degrade over time due to heat exposure, voltage spikes, and normal aging. Understanding the different failure modes helps you diagnose accurately and explain the repair to the customer.

Gradual degradation - The most common failure mode. Capacitors slowly lose capacitance over their lifetime. A capacitor rated at 45 MFD may test at 40 MFD after 5 years, 35 MFD after 8 years, and 25 MFD after 12 years. The motor struggles increasingly as capacitance drops. The acceptable tolerance is +/- 6% of the rated value. A 45 MFD capacitor should test between 42.3 and 47.7 MFD to be considered good.

Open failure - The capacitor completely loses its ability to store energy. It tests at 0 MFD. The motor will hum but not start (if the start winding depends on the capacitor) or will run at reduced efficiency with high amp draw.

Short circuit failure - Internal plates short together. The capacitor may bulge, leak oil, or even rupture. A shorted capacitor can damage the motor or blow the circuit fuse. Shorted capacitors sometimes cause the compressor to trip on overload within seconds of starting.

Intermittent failure - The capacitor tests within specification when cool but fails when hot. This is the most frustrating failure to diagnose because it works perfectly when the technician arrives and the system has cooled down. If a customer reports intermittent problems on hot days and the capacitor tests marginal (within spec but near the low limit), replace it.

+/- 6%
Acceptable MFD Tolerance
45 MFD
Common Compressor Run Cap Size
5 MFD
Common Condenser Fan Cap Size
370/440V
Common Run Capacitor Voltage Rating

Capacitor Testing Procedure

Step 1: Safety first. De-energize the system. Discharge the capacitor using a bleed-down resistor (20,000 ohm, 5-watt resistor across the terminals). Verify 0V with a voltmeter.

Step 2: Disconnect wires. Remove at least one wire from each terminal to isolate the capacitor from the circuit. If you test a capacitor while it is still connected to motor windings, the winding resistance will affect the reading.

Step 3: Test MFD. Set your multimeter to the capacitance function (MFD or uF). Touch the probes to the capacitor terminals. The meter will briefly charge the capacitor and display its capacitance. Compare to the rated value printed on the label. Within +/- 6% is acceptable.

Step 4: Dual run capacitor testing. A dual run capacitor has three terminals: C (common), HERM (compressor), and FAN (condenser fan). Test between C and HERM for the compressor section and between C and FAN for the fan section. Both sections must test within tolerance.

1
De-energize & Discharge
Power off, bleed-down resistor, verify 0V
2
Disconnect Wires
Isolate capacitor from motor windings
3
Test MFD
Meter on capacitance function, compare to label
4
Evaluate
Within +/- 6% = good; below = replace

Replacement Guidelines

When replacing capacitors:

  • Match the MFD rating exactly. A higher or lower MFD value changes the motor's operating characteristics.
  • Match or exceed the voltage rating. A 370V capacitor can be replaced with a 440V capacitor of the same MFD, but never replace with a lower voltage rating.
  • Replace with quality components. Low-cost import capacitors may have shorter life spans and higher failure rates.
  • If one section of a dual capacitor fails, replace the entire capacitor. The other section is the same age and likely to fail soon.
💡

The "Swollen Top" Test

A healthy run capacitor has a flat top. A capacitor with a bulged or domed top has experienced internal gas expansion from overheating or dielectric breakdown and should be replaced immediately, even if it still tests within MFD tolerance. The bulge indicates the capacitor is in the process of failing and may rupture.

Key Takeaway

Capacitors must test within +/- 6% of their rated MFD to be considered good. Always discharge before testing, isolate from motor windings, and check dual capacitors at both sections (C-HERM and C-FAN). A bulged top means replacement regardless of MFD reading. Match MFD exactly and match or exceed voltage rating when replacing. Intermittent capacitor failures on hot days are real - replace marginal capacitors proactively.