Skip to content
Module 5 sur 10 280m 14 exam Qs

Branch Circuits & Wiring Methods

Conductor sizing, ampacity derating, conduit types and bending rules, NMD90 cable, box fill calculations, and voltage drop.

  • State the minimum conductor sizes for 15A and 20A branch circuits
  • Explain conductor ampacity derating for conduit fill and ambient temperature
  • Identify common Canadian wiring methods including NMD90, EMT, and TECK cable
  • Apply conduit bending rules and box fill calculations per the CEC
  • Calculate voltage drop and determine minimum burial depths for underground cables

Leçon 1

Conductor Sizing, Ampacity & Derating

Minimum Conductor Sizes

The CEC establishes minimum conductor sizes for branch circuits based on the overcurrent protection rating. The 2024 CE Code (Section 4) formally recognizes both AWG/kcmil and mm2 sizing - both systems are equally valid and you may encounter either on drawings and specifications.

14 AWG
Minimum for any branch circuit (CEC)
14 AWG
Maximum 15A overcurrent protection
12 AWG
Minimum for 20A branch circuit
10 AWG
Minimum for 30A branch circuit

According to the CEC, the minimum size conductor permitted for branch circuits is 14 AWG. A 14 AWG copper conductor is rated for a maximum of 15 amps of overcurrent protection. The overcurrent protection for a 15 amp branch circuit using 14 AWG copper conductors should not exceed 15 amps.

For a 20 amp branch circuit, the minimum conductor size is 12 AWG copper.

AWG to mm2 Conductor Size Equivalents

Section 4 of the 2024 CE Code formally recognizes mm2 sizing alongside AWG/kcmil. The mm2 cross-sectional area values are the metric equivalents used in specifications, drawings, and imported equipment documentation:

AWG / kcmil mm2 (approx.) Common Use
14 AWG 2.5 mm2 15A branch circuits (residential)
12 AWG 4 mm2 20A branch circuits
10 AWG 6 mm2 30A branch circuits
8 AWG 10 mm2 40-50A circuits
6 AWG 16 mm2 60A circuits, EGC for 200A service
4 AWG 25 mm2 100A feeders
2 AWG 35 mm2 125A feeders
1/0 AWG 50 mm2 150A feeders
3/0 AWG 95 mm2 200A service entrance
💡

AWG vs mm2 on the Exam

The 2024 CE Code recognizes both sizing systems equally. A specification calling for 2.5 mm2 is the same as 14 AWG, and 4 mm2 equals 12 AWG. Memorize the key pairs: 14 AWG = 2.5 mm2, 12 AWG = 4 mm2, 10 AWG = 6 mm2. These three cover the vast majority of residential branch circuit work.

Ampacity

The ampacity of a conductor is defined as the maximum current it can carry continuously under the conditions of use without exceeding its temperature rating. Ampacity depends on:

  • Conductor material (copper vs. aluminum)
  • Conductor size (AWG or kcmil)
  • Insulation temperature rating (60C, 75C, or 90C)
  • Installation conditions (ambient temperature, conduit fill)

CEC Table 2 provides the ampacity values for conductors at a standard ambient temperature of 30C.

Derating

Derating conductor ampacity is required to account for heat buildup in conduit or high ambient temperatures. When multiple current-carrying conductors are installed in the same conduit or cable, they generate heat that cannot dissipate as easily. The CEC requires ampacity correction in two situations:

Conduit Fill Derating

4-6 conductors: 80% of table ampacity

7-24 conductors: 70% of table ampacity

25-42 conductors: 60% of table ampacity

Applies when more than 3 current-carrying conductors share a raceway

Ambient Temperature Correction

31-35C: Multiply by 0.94

36-40C: Multiply by 0.87

41-45C: Multiply by 0.79

Applies when ambient temperature exceeds 30C

Key Takeaway

The minimum branch circuit conductor is 14 AWG (2.5 mm2) (rated for 15A max). A 20A circuit requires 12 AWG (4 mm2) minimum. The 2024 CE Code formally recognizes mm2 sizing alongside AWG/kcmil. Conductor ampacity is the maximum continuous current a conductor can carry. Derating accounts for heat buildup from conduit fill or high ambient temperatures.